Toxalert GVU-3 Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
SPECIFICATIONS
Input Power: 120 VAC, 60 Hz, 1A (fused)
Relay Contacts: 24 VAC, 2A resistive, 1.5 inductive
Discrete Clock Settings: 1 minute intervals
Automatic Ventilation Cycle Upon
Power Restoration: User adjustable 1 to 8 minutes
Finish: Control Unit: Gray enamel
Enclosure: Nema 1 standard, others available
Dimensions: 14” H x 12” W x 4” D.
(305mm x 102 mm)
Weight: 8 lbs. (3.6 kg)
INSTALLATION INSTRUCTIONS
1. INTRODUCTION
Your TOXALERT Ventilation Control System incorporates the
latest in solid state technology to give you maximum reliability
and perfomance. The system alarm set point can be adjusted to
activate fans upon detection of an unsafe concentration of CO,
CO
2
, NO
2
,VOC air quality. In addition, a user-definable hourly
repeat cycle is provided, allowing time-based, as well as gas-
based fan activation. In both modes of fan control, the “on”
time is user-adjustable 1 to 8 minutes in one minute increments.
For optimum performance, install, burn-in, calibrate and check
out your TOXALERT exactly as instructed. If your
TOXALERT can’t be calibrated or fails checkout, please
contact your local representative or TOXALERT
International for servicing.
2. INSTALLATION
Refer to figures 1, 2 and 3, and install and connect the
TOXALERT sensors and control units as follows:
GVU-CO SENSING UNITS
1) Open the door using the key provided. Next lift off the front
door by sliding it up the pins of the hinges. Put it aside.
2) Locate a mounting location away from drafts, away from
direct fresh air intakes, and mount vertically on wall or
support column approximately 5 to 6 feet above floor.
3) Mount base with hinge pins along left side by using
mounting holes (4 are available).
4) A wiring access hole must be added to the base anywhere
around the bottom or right side. Do not place an access hole
on the hinge side of the base, since, if conduit is used, this
may restrict the opening of the door. If conduit is to be used,
use a chassis punch to match the required fitting size.
5) Remove any metal chips and burrs from enclosure.
6) Place the cover onto the hinges of the base.
See separate data sheet for installation instructions of
GVU-CO2, GVU-NO2 and GVU-VOC.
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
Vue de la page 1
1 2 3 4

Commentaires sur ces manuels

Pas de commentaire